VOLTAGE REGULATION
5 June 2014
By : Ernst de Villiers
Layout of Presentation
• Problem Statement
• Construction of the Voltage Regulator
• Basic theory of Voltage Regulation
• Implementation of Voltage Regulators
• Voltage Regulators Vs. Load Tap Changers
• Case Study – Commissioning
2
3
Problem Statement
• An ideal electric power system
would supply constant voltage at
rated value for every piece of
equipment.
• Power systems cannot deliver a
constant voltage level due to
line losses caused by the line
impedance and an increase in
load density.
• When voltage profile limits are
exceeded, either performance or
equipment life is sacrificed.
How Voltage drops are created
• MV distribution feeders are designed short enough and/or are loaded
so that the voltage profile is kept within specific limits.
4
Medium length line model
Properly-designed distribution feeder
Problem Statement
• To minimize the time and expense of serving the new load, the length
of the feeder is usually extended. Hence, in most cases, the feeder
develops an unacceptable voltage drop as shown in the figure below.
5
Increase of load density and feeder length
results in an unacceptable voltage drop.
Solution – The Voltage Regulator
6
• A Voltage Regulator can continuously monitor the output voltage
and automatically adjust itself by changing taps until the desired
voltage is obtained .
Operational Theory
• A voltage regulator holds line voltage within predetermined limits and
assures the proper operation of connected loads
• To understand how a regulator operates, one must first understand
how a two-winding transformer operates.
7
Transformer Model
Ideal Transformer
• These two independent windings can then be connected so that their
voltages may aid or oppose one another.
• Thus, the output terminal voltage can either be measured as the sum
of the two voltages or the difference between them.
• Therefore; transformer becomes a auto transformer with the ability to
raise or lower the primary or system voltage
8
Operation Theory
Step-down Trfr Step-up Trfr
9 9
How does a Voltage Regulator work?
A single-phase regulator is represented by the autotransformer in
the figure below.
•Series Winding – Low voltage Winding
•Shunt Winding – High Voltage Winding
Voltage Regulator Diagram
10
How does a Voltage Regulator work?
By reversing the polarity of the series winding, the autotransformer
can boost (increase) or buck (decrease) the output voltage with
respect to the input voltage
Step-down Trfr
Step-up Trfr
Voltage Regulator Diagram
11
How does a Voltage Regulator work?
Polarity reversing is achieved via a reversing switch. An on-load
tap-changer connects a variable number of turns of the series
winding into the circuit, thereby allowing small increments of
voltage change.
2015-08-11 12
Schematic Diagram – 32 step Voltage
Regulator
Non Bridging Equalizing Winding and
Reactor
• The preventive autotransformer is required in order to smoothen the
transient encountered when switching taps.
• Thus, decreasing the interrupted current as the tap changer taps.
• Preventing the regulator from being disconnected from the circuit each
time the tap is changed.
13
Voltage Regulator Parts
14
Bushing Construction
15
Bushings
• The preferred bushing terminals are smooth, hot-dip tinned, copper cylindrical
stems provided with bimetallic clamps that are suitable for accepting
aluminum or copper conductors of 6 mm to 15 mm diameter.
16
BUSHING SPECIFICATION FOR POLEMOUNTED, SINGLE-PHASE, STEP, AUTOMATIC VOLTAGE REGULATORS
MOV Surge Arrester
17
At normal voltage the MOV disk is an
insulator and will not conduct current.
But at higher voltages caused by surges
(faults/ lightning) , it becomes a conductor.
Thus, the arrester protects the series
winding from surges.
MOV Surge Arrester
11 kV Application 22 kV Application
MCOV: > 2.5 kV >5 kV
Residual voltage: Ures <10.5 kV <20 kV
Rated discharge current 10 kA 10 kA
Creepage 31mm/kV 31mm/kV
18
According to Specification 34-2110:
The surge arrester shall comply with the following parameters:
Internal Parts – QD8 Quick Drive tap-
changer
19
Reactors
• A bridging reactor is required to maintain continuity during a tap
change and to provide impedance for limiting the amount of current to
be interrupted by the tap changer.
20
Core Type ReactorShell Type Reactor
Core type is designed that the two coils are interlaced resulting in minimal
impedance-to-load current flow and therefore minimal voltage drop.
CL6A Control Board
21
CL6A Control Board
22
Drag-Hand
23
The Yellow tap indicating needle drags minimum and maximum needles.
24
How does a Voltage Regulator work?
Type of Regulators
Two types of regulators:
•Type A
•Type B step-voltage regulators are predominately used for distribution
lines outside of the substation and lateral circuits.
25
Type A Regulator
The tapped series winding is located on the load side of the shunt
winding, and by adjusting those taps the output load voltage
changes.
26
Type B Regulator
The tapped series winding is located on the source side of the
shunt (excitation) winding, and by adjusting those taps the output
load voltage changes.
Regulator Ratio
27
Typical maximum boosts and bucks are ±10%.
What will aR and nt=N2/N1 be in the maximum boost and buck positions?
9091.1
1
2

N
N
aR

0909.9091.1
1
2

N
N
Voltage Regulation Per Step
• According to AVR Spec 34-2110 – Regulators will provide 10%
regulation with 32 step (16 buck and 16 boost).
• Since 16 steps provides 10% boost (or buck), then a single step will
result in a voltage change of 1/16 of 10%, which is:
• Since “% voltage” is Per Unit voltage x 100, the Per Unit voltage
change per step is
• So we obtain 0.00625 Per Unit voltage change per step.
28
• The ratio (N2/N1)effective is then given by the pu voltage change per step
times the number of steps (Tap):
• Note that if Tap is 0, then the effective turns ratio is 0. In this case,
there is no boost, and VL=VS.
29
Voltage Regulation Per Step
Line Drop Compensation (LDC)
• Allows a constant voltage to be maintained at a load centre remote
from the regulator.
30
2015-08-11 31
Wiring Diagram – CT Circuit Protection
How is it implemented?
• Two or three single-phase regulators banked together make it possible
to regulate the voltage of a three-phase system.
32
Closed-Delta Open-Delta
3 Voltage Regulators 2 Voltage Regulators
15% Regulation of Input
Voltage
10% Regulation of Input
Voltage
Mostly used in ECOU Cost effective
Connection Configuration
Two or three single-phase regulators banked together make it possible to
regulate the voltage of a three-phase system.
Closed Delta Implementation Open Delta Implementation
33
Configuration
34
Open-Delta connection
Closed-Delta connection
How ratings are selected
Two parameters are necessary to elect a voltage regulator:
1) Rated Voltage
2) Rated Current
• Rated Voltage: It must be equal to or higher than the system nominal
voltage.
• Rated Current: It must be equal to or higher than the maximum load
current at the place that regulator is going to be installed.
35
Regulator Tests
• The AVR shall have been type tested in accordance with, and found to
comply with, the following requirements of ANSI/IEEE C57.15.
• Impulse test;
• Temperature rise;
• Short-circuit tests – KA rating-3 seconds amps;
• Insulation testing – Megger
36
Where to Apply
1) On existing feeders with voltage drop problems
• This is a common application of voltage regulators.
• They are installed before the point that the voltage drop problem starts
under heavy load conditions.
37
38
Where to Apply
2) Important laterals from a main feeder can be effectively
controlled with regulators.
39
3) To serve a remotely located load
These types of loads can be economically and quickly served by extending
the existing feeder and installing voltage regulators to correct for the voltage
drop in the extension.
Where to Apply
Operating sequence to put a regulator bank
on bypass – Spec 34-1436
1. Apply all regulators on neutral tap
2. Check regulator incoming and outgoing links to be closed.
3. Close regulator bypass links.
4. Open regulator outgoing links.
5. Open regulator incoming links.
6. Test regulator to be dead.
7. Apply relevant earths
40
Operating sequence to put a regulator bank
back in service - Spec 34-1436
1. Remove all earths.
2. Check regulator bypass links to be closed.
3. Close regulator incoming links.
4. Ensure that regulators is on neutral tap.
5. Close regulator bank outgoing links.
6. Open regulator bank bypass links.
7. Put regulator on auto
41
42
Voltage Regulators vs. Load Tap Changers
• The basic function of an electrical utility is to supply power to
customers.
• With system losses and voltage sags that must be corrected by
regulation in order to stay within the voltage limit.
• Even in a real world of ongoing maintenance and occasional
component failure, objectives of minimizing outage time and
limiting failures can be realized.
3 Single phase Regulators Transformer + LTC
One phase offline- replacement of only
one regulator unit.
Failure of one phase of the TC, entire
unit removed – all phase effected.
43
Voltage Regulators vs. Load Tap Changers
One spare regulator unit can be utilized on any of the phases if
maintenance is required.
Full maintenance can be completed without diminishing system
service.
Each Single-phase unit has an independent control to react to
the voltage variances of the phase.
44
Voltage Regulators vs. Load Tap Changers
Unbalanced phase voltages – single phase units can respond
individually to these independent feeder models.
By separating each phase into its own unit, every unit is made smaller
and easier to handle.
Bypass switching provides easy installation and the ability to remove a
regulator without dropping the entire bus or feeder.
45
Voltage Regulators vs. Load Tap Changers
Cost Comparison
46
• There are some choices to be made in how to regulate voltage; some of
these choices can require significant capital expenditures.
Study done by Cooper Power Systems Ref. Number R225-90-21
Prospect - Kaysers Beach Voltage Regulator
• 11kV Pine conductor line that interconnects with Prospect - Gately line
via a normally open point situated at structure PRO-KBH-79.
• Approximately 2078 number of customers – 83km line.
• This feeder is at its voltage limit due to the normal growth from supply
upgrades and new developments in the area.
• The acceptable voltage limit for this feeder is 95% of nominal.
Currently, the minimum voltage is 95%, hence the initiation of this
project.
47
Commissioning Test Sheet
• Procedure 34 – 1218 : Presents the Commissioning Check Sheet
48
VOLTAGE REGULATOR
COMMISSIONING CHECK SHEET
WORKS ORDER #
COMMISSIONED
BY:
DATE:
LOCATION:
REGULATOR DETAILS
VR SERIAL #: R =
W=
B=
KV RATING:
CONTROL MODEL: AMP RATING:
Cat Numbre R=
W=
B=
INLAND/COASTAL:
ON-SITE CHECKS
ACTION Yes No COMMENT/VALUE
1. Verify that HV Connections are correct
(2 x VR - Open Delta or 3 x VR - Closed Delta)
2. Verify Regulator & Line voltage is the same
(Name plate & line voltage)
3. Check that Regulator is on By-Pass & Isolated
(By-Pass CLOSED & All Links OPEN)
4. Check that Regulators & Controls are EARTHED
(Individually to same earthing point )
5. Check that all HV connection are TIGHT
6. Check that Regulator is in NEUTRAL position
(Position indicator & FC12)
7. Set Power switch & control switch to OFF position
(All three switches in middle )
8. In Control back panel OPEN knife switch V1, C (and V6 if
present), (pulled out)
(Terminal links)
9. Insulation test must be done
( 5KV Megger )
Ohm
10. Close Source-Load (SL) incoming link
(Operator to close)
CHECK THAT ALL 3 PHASES ARE PRESENT IN AND OUT
11. Measure Voltage terminal V1 to earth and confirm approx
118-122VAC
(If out of range, abort commissioning and investigate)
Volt
R = W= B=
12. In Control back panel CLOSE knife switch V1 (and V6 if
present), (pushed in)
(Terminal links)
13. Check that knife switch “C” is open
(Terminal links)
14. Set Power Switch to INTERNAL
(Power switch up)
Set Clock
( FC 50 )
15. Check NEUTRAL light is on
16. Check settings according to settings sheet (Annexure)
(Note: for testing of up/down tap, set FC56 to Lock Forward)
17. Set control switch to MANUAL
(Control switch down)
18. Manually RAISE tap till Out of Band indication ON
19. Set control switch to AUTO
(Control switch up)
20. Confirm auto-tap LOWER & Out of Band indication OFF
(FC3 Delay plus 2sec per tap)
• Evaluation of losses in step-voltage regulators is increasingly a major
consideration when evaluating competitive alternatives.
. Some of the areas that should be evaluated in addition to the cost :
• Maintenance,
• Installation and Operation,
• Technical support,
• Dielectric strength,
• Short circuit strength,
• Losses
49
Regulator Characteristics
Thank you
Open for Discussion

Más contenido relacionado

La actualidad más candente

Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniquesrifat maryum
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentationAzhar Abbas
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area SystemManash Deka
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage ControlYashvi Mehta
 
3 reactive power and voltage control
3 reactive power and voltage control3 reactive power and voltage control
3 reactive power and voltage control8141245710
 
Power quality notes unit 1
Power quality notes unit  1 Power quality notes unit  1
Power quality notes unit 1 Dilip kumar
 
FACTS DEVICES
FACTS DEVICESFACTS DEVICES
FACTS DEVICESamit8847
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptxUtthejNani1
 
High Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionHigh Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionZunAib Ali
 
Chapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and currentChapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and currentmukund mukund.m
 
Classification Of Power System Stability
Classification Of Power System StabilityClassification Of Power System Stability
Classification Of Power System StabilityAravind Shaji
 

La actualidad más candente (20)

statcom
statcomstatcom
statcom
 
IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
On load tap changer
On load tap changerOn load tap changer
On load tap changer
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentation
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area System
 
Methods of Voltage Control
Methods of Voltage ControlMethods of Voltage Control
Methods of Voltage Control
 
Transformer
TransformerTransformer
Transformer
 
Single line diagram
Single line diagramSingle line diagram
Single line diagram
 
3 reactive power and voltage control
3 reactive power and voltage control3 reactive power and voltage control
3 reactive power and voltage control
 
upfc
upfcupfc
upfc
 
Power factor
Power factorPower factor
Power factor
 
Power factor improvement
Power factor improvement Power factor improvement
Power factor improvement
 
Power quality notes unit 1
Power quality notes unit  1 Power quality notes unit  1
Power quality notes unit 1
 
FACTS DEVICES
FACTS DEVICESFACTS DEVICES
FACTS DEVICES
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
 
High Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionHigh Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmission
 
Chapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and currentChapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and current
 
Classification Of Power System Stability
Classification Of Power System StabilityClassification Of Power System Stability
Classification Of Power System Stability
 

Similar a Voltage Regulation

Current mode circuits & voltage mode circuits
Current mode circuits & voltage mode circuits Current mode circuits & voltage mode circuits
Current mode circuits & voltage mode circuits Kevin Gajera
 
Different method of frequency and voltage control
Different method of frequency and voltage controlDifferent method of frequency and voltage control
Different method of frequency and voltage control8141245710
 
DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLyohannes feleke
 
Electric-Traction-Railways.ppt
Electric-Traction-Railways.pptElectric-Traction-Railways.ppt
Electric-Traction-Railways.pptssuserf805c8
 
Switchgear & Rectifier ppt
Switchgear & Rectifier pptSwitchgear & Rectifier ppt
Switchgear & Rectifier pptvikas kumar
 
Psoc voltage control 2018
Psoc voltage control 2018Psoc voltage control 2018
Psoc voltage control 2018Mohamed Samir
 
Review of Step down Converter with Efficient ZVS Operation
Review of Step down Converter with Efficient ZVS OperationReview of Step down Converter with Efficient ZVS Operation
Review of Step down Converter with Efficient ZVS OperationIJRST Journal
 
Ic voltage regulators
Ic voltage regulatorsIc voltage regulators
Ic voltage regulatorsAnita Thattil
 
Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line CompensationAnakin Akshat Assal
 
An Adaptive Zero Voltage Mechanism for Boost Converter
An Adaptive Zero Voltage Mechanism for Boost ConverterAn Adaptive Zero Voltage Mechanism for Boost Converter
An Adaptive Zero Voltage Mechanism for Boost ConverterIOSR Journals
 
Ch_6 Regulated Power Supply (1).ppt
Ch_6 Regulated Power Supply (1).pptCh_6 Regulated Power Supply (1).ppt
Ch_6 Regulated Power Supply (1).pptJeelBhanderi4
 
1660034363151685.pptx
1660034363151685.pptx1660034363151685.pptx
1660034363151685.pptxPradip khatri
 
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMLOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMASWATHYSANAND1
 
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTERSOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTERAbhin Mohan
 
Schuler Electronics Instructor CH15 regulated power supplies.ppt
Schuler Electronics Instructor CH15 regulated power supplies.pptSchuler Electronics Instructor CH15 regulated power supplies.ppt
Schuler Electronics Instructor CH15 regulated power supplies.pptSagarPatel532644
 

Similar a Voltage Regulation (20)

T&D_Unit V.pdf
T&D_Unit V.pdfT&D_Unit V.pdf
T&D_Unit V.pdf
 
Current mode circuits & voltage mode circuits
Current mode circuits & voltage mode circuits Current mode circuits & voltage mode circuits
Current mode circuits & voltage mode circuits
 
Different method of frequency and voltage control
Different method of frequency and voltage controlDifferent method of frequency and voltage control
Different method of frequency and voltage control
 
PQH 3rd chapter.pptx
PQH 3rd chapter.pptxPQH 3rd chapter.pptx
PQH 3rd chapter.pptx
 
DISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROLDISTRIBUTION SYSTEM OPERATION AND CONTROL
DISTRIBUTION SYSTEM OPERATION AND CONTROL
 
EDS Unit 6.pptx
EDS Unit 6.pptxEDS Unit 6.pptx
EDS Unit 6.pptx
 
Electric-Traction-Railways.ppt
Electric-Traction-Railways.pptElectric-Traction-Railways.ppt
Electric-Traction-Railways.ppt
 
Switchgear & Rectifier ppt
Switchgear & Rectifier pptSwitchgear & Rectifier ppt
Switchgear & Rectifier ppt
 
Psoc voltage control 2018
Psoc voltage control 2018Psoc voltage control 2018
Psoc voltage control 2018
 
Untitled document.PDF
Untitled document.PDFUntitled document.PDF
Untitled document.PDF
 
Review of Step down Converter with Efficient ZVS Operation
Review of Step down Converter with Efficient ZVS OperationReview of Step down Converter with Efficient ZVS Operation
Review of Step down Converter with Efficient ZVS Operation
 
Ic voltage regulators
Ic voltage regulatorsIc voltage regulators
Ic voltage regulators
 
Power System Control And Line Compensation
Power System Control And Line CompensationPower System Control And Line Compensation
Power System Control And Line Compensation
 
An Adaptive Zero Voltage Mechanism for Boost Converter
An Adaptive Zero Voltage Mechanism for Boost ConverterAn Adaptive Zero Voltage Mechanism for Boost Converter
An Adaptive Zero Voltage Mechanism for Boost Converter
 
Ch_6 Regulated Power Supply (1).ppt
Ch_6 Regulated Power Supply (1).pptCh_6 Regulated Power Supply (1).ppt
Ch_6 Regulated Power Supply (1).ppt
 
unit_2.ppt
unit_2.pptunit_2.ppt
unit_2.ppt
 
1660034363151685.pptx
1660034363151685.pptx1660034363151685.pptx
1660034363151685.pptx
 
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMLOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
 
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTERSOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
 
Schuler Electronics Instructor CH15 regulated power supplies.ppt
Schuler Electronics Instructor CH15 regulated power supplies.pptSchuler Electronics Instructor CH15 regulated power supplies.ppt
Schuler Electronics Instructor CH15 regulated power supplies.ppt
 

Voltage Regulation

  • 1. VOLTAGE REGULATION 5 June 2014 By : Ernst de Villiers
  • 2. Layout of Presentation • Problem Statement • Construction of the Voltage Regulator • Basic theory of Voltage Regulation • Implementation of Voltage Regulators • Voltage Regulators Vs. Load Tap Changers • Case Study – Commissioning 2
  • 3. 3 Problem Statement • An ideal electric power system would supply constant voltage at rated value for every piece of equipment. • Power systems cannot deliver a constant voltage level due to line losses caused by the line impedance and an increase in load density. • When voltage profile limits are exceeded, either performance or equipment life is sacrificed.
  • 4. How Voltage drops are created • MV distribution feeders are designed short enough and/or are loaded so that the voltage profile is kept within specific limits. 4 Medium length line model Properly-designed distribution feeder
  • 5. Problem Statement • To minimize the time and expense of serving the new load, the length of the feeder is usually extended. Hence, in most cases, the feeder develops an unacceptable voltage drop as shown in the figure below. 5 Increase of load density and feeder length results in an unacceptable voltage drop.
  • 6. Solution – The Voltage Regulator 6 • A Voltage Regulator can continuously monitor the output voltage and automatically adjust itself by changing taps until the desired voltage is obtained .
  • 7. Operational Theory • A voltage regulator holds line voltage within predetermined limits and assures the proper operation of connected loads • To understand how a regulator operates, one must first understand how a two-winding transformer operates. 7 Transformer Model Ideal Transformer
  • 8. • These two independent windings can then be connected so that their voltages may aid or oppose one another. • Thus, the output terminal voltage can either be measured as the sum of the two voltages or the difference between them. • Therefore; transformer becomes a auto transformer with the ability to raise or lower the primary or system voltage 8 Operation Theory Step-down Trfr Step-up Trfr
  • 9. 9 9 How does a Voltage Regulator work? A single-phase regulator is represented by the autotransformer in the figure below. •Series Winding – Low voltage Winding •Shunt Winding – High Voltage Winding Voltage Regulator Diagram
  • 10. 10 How does a Voltage Regulator work? By reversing the polarity of the series winding, the autotransformer can boost (increase) or buck (decrease) the output voltage with respect to the input voltage Step-down Trfr Step-up Trfr Voltage Regulator Diagram
  • 11. 11 How does a Voltage Regulator work? Polarity reversing is achieved via a reversing switch. An on-load tap-changer connects a variable number of turns of the series winding into the circuit, thereby allowing small increments of voltage change.
  • 12. 2015-08-11 12 Schematic Diagram – 32 step Voltage Regulator
  • 13. Non Bridging Equalizing Winding and Reactor • The preventive autotransformer is required in order to smoothen the transient encountered when switching taps. • Thus, decreasing the interrupted current as the tap changer taps. • Preventing the regulator from being disconnected from the circuit each time the tap is changed. 13
  • 16. Bushings • The preferred bushing terminals are smooth, hot-dip tinned, copper cylindrical stems provided with bimetallic clamps that are suitable for accepting aluminum or copper conductors of 6 mm to 15 mm diameter. 16 BUSHING SPECIFICATION FOR POLEMOUNTED, SINGLE-PHASE, STEP, AUTOMATIC VOLTAGE REGULATORS
  • 17. MOV Surge Arrester 17 At normal voltage the MOV disk is an insulator and will not conduct current. But at higher voltages caused by surges (faults/ lightning) , it becomes a conductor. Thus, the arrester protects the series winding from surges.
  • 18. MOV Surge Arrester 11 kV Application 22 kV Application MCOV: > 2.5 kV >5 kV Residual voltage: Ures <10.5 kV <20 kV Rated discharge current 10 kA 10 kA Creepage 31mm/kV 31mm/kV 18 According to Specification 34-2110: The surge arrester shall comply with the following parameters:
  • 19. Internal Parts – QD8 Quick Drive tap- changer 19
  • 20. Reactors • A bridging reactor is required to maintain continuity during a tap change and to provide impedance for limiting the amount of current to be interrupted by the tap changer. 20 Core Type ReactorShell Type Reactor Core type is designed that the two coils are interlaced resulting in minimal impedance-to-load current flow and therefore minimal voltage drop.
  • 23. Drag-Hand 23 The Yellow tap indicating needle drags minimum and maximum needles.
  • 24. 24 How does a Voltage Regulator work? Type of Regulators Two types of regulators: •Type A •Type B step-voltage regulators are predominately used for distribution lines outside of the substation and lateral circuits.
  • 25. 25 Type A Regulator The tapped series winding is located on the load side of the shunt winding, and by adjusting those taps the output load voltage changes.
  • 26. 26 Type B Regulator The tapped series winding is located on the source side of the shunt (excitation) winding, and by adjusting those taps the output load voltage changes.
  • 27. Regulator Ratio 27 Typical maximum boosts and bucks are ±10%. What will aR and nt=N2/N1 be in the maximum boost and buck positions? 9091.1 1 2  N N aR  0909.9091.1 1 2  N N
  • 28. Voltage Regulation Per Step • According to AVR Spec 34-2110 – Regulators will provide 10% regulation with 32 step (16 buck and 16 boost). • Since 16 steps provides 10% boost (or buck), then a single step will result in a voltage change of 1/16 of 10%, which is: • Since “% voltage” is Per Unit voltage x 100, the Per Unit voltage change per step is • So we obtain 0.00625 Per Unit voltage change per step. 28
  • 29. • The ratio (N2/N1)effective is then given by the pu voltage change per step times the number of steps (Tap): • Note that if Tap is 0, then the effective turns ratio is 0. In this case, there is no boost, and VL=VS. 29 Voltage Regulation Per Step
  • 30. Line Drop Compensation (LDC) • Allows a constant voltage to be maintained at a load centre remote from the regulator. 30
  • 31. 2015-08-11 31 Wiring Diagram – CT Circuit Protection
  • 32. How is it implemented? • Two or three single-phase regulators banked together make it possible to regulate the voltage of a three-phase system. 32 Closed-Delta Open-Delta 3 Voltage Regulators 2 Voltage Regulators 15% Regulation of Input Voltage 10% Regulation of Input Voltage Mostly used in ECOU Cost effective
  • 33. Connection Configuration Two or three single-phase regulators banked together make it possible to regulate the voltage of a three-phase system. Closed Delta Implementation Open Delta Implementation 33
  • 35. How ratings are selected Two parameters are necessary to elect a voltage regulator: 1) Rated Voltage 2) Rated Current • Rated Voltage: It must be equal to or higher than the system nominal voltage. • Rated Current: It must be equal to or higher than the maximum load current at the place that regulator is going to be installed. 35
  • 36. Regulator Tests • The AVR shall have been type tested in accordance with, and found to comply with, the following requirements of ANSI/IEEE C57.15. • Impulse test; • Temperature rise; • Short-circuit tests – KA rating-3 seconds amps; • Insulation testing – Megger 36
  • 37. Where to Apply 1) On existing feeders with voltage drop problems • This is a common application of voltage regulators. • They are installed before the point that the voltage drop problem starts under heavy load conditions. 37
  • 38. 38 Where to Apply 2) Important laterals from a main feeder can be effectively controlled with regulators.
  • 39. 39 3) To serve a remotely located load These types of loads can be economically and quickly served by extending the existing feeder and installing voltage regulators to correct for the voltage drop in the extension. Where to Apply
  • 40. Operating sequence to put a regulator bank on bypass – Spec 34-1436 1. Apply all regulators on neutral tap 2. Check regulator incoming and outgoing links to be closed. 3. Close regulator bypass links. 4. Open regulator outgoing links. 5. Open regulator incoming links. 6. Test regulator to be dead. 7. Apply relevant earths 40
  • 41. Operating sequence to put a regulator bank back in service - Spec 34-1436 1. Remove all earths. 2. Check regulator bypass links to be closed. 3. Close regulator incoming links. 4. Ensure that regulators is on neutral tap. 5. Close regulator bank outgoing links. 6. Open regulator bank bypass links. 7. Put regulator on auto 41
  • 42. 42 Voltage Regulators vs. Load Tap Changers • The basic function of an electrical utility is to supply power to customers. • With system losses and voltage sags that must be corrected by regulation in order to stay within the voltage limit. • Even in a real world of ongoing maintenance and occasional component failure, objectives of minimizing outage time and limiting failures can be realized.
  • 43. 3 Single phase Regulators Transformer + LTC One phase offline- replacement of only one regulator unit. Failure of one phase of the TC, entire unit removed – all phase effected. 43 Voltage Regulators vs. Load Tap Changers One spare regulator unit can be utilized on any of the phases if maintenance is required. Full maintenance can be completed without diminishing system service. Each Single-phase unit has an independent control to react to the voltage variances of the phase.
  • 44. 44 Voltage Regulators vs. Load Tap Changers
  • 45. Unbalanced phase voltages – single phase units can respond individually to these independent feeder models. By separating each phase into its own unit, every unit is made smaller and easier to handle. Bypass switching provides easy installation and the ability to remove a regulator without dropping the entire bus or feeder. 45 Voltage Regulators vs. Load Tap Changers
  • 46. Cost Comparison 46 • There are some choices to be made in how to regulate voltage; some of these choices can require significant capital expenditures. Study done by Cooper Power Systems Ref. Number R225-90-21
  • 47. Prospect - Kaysers Beach Voltage Regulator • 11kV Pine conductor line that interconnects with Prospect - Gately line via a normally open point situated at structure PRO-KBH-79. • Approximately 2078 number of customers – 83km line. • This feeder is at its voltage limit due to the normal growth from supply upgrades and new developments in the area. • The acceptable voltage limit for this feeder is 95% of nominal. Currently, the minimum voltage is 95%, hence the initiation of this project. 47
  • 48. Commissioning Test Sheet • Procedure 34 – 1218 : Presents the Commissioning Check Sheet 48 VOLTAGE REGULATOR COMMISSIONING CHECK SHEET WORKS ORDER # COMMISSIONED BY: DATE: LOCATION: REGULATOR DETAILS VR SERIAL #: R = W= B= KV RATING: CONTROL MODEL: AMP RATING: Cat Numbre R= W= B= INLAND/COASTAL: ON-SITE CHECKS ACTION Yes No COMMENT/VALUE 1. Verify that HV Connections are correct (2 x VR - Open Delta or 3 x VR - Closed Delta) 2. Verify Regulator & Line voltage is the same (Name plate & line voltage) 3. Check that Regulator is on By-Pass & Isolated (By-Pass CLOSED & All Links OPEN) 4. Check that Regulators & Controls are EARTHED (Individually to same earthing point ) 5. Check that all HV connection are TIGHT 6. Check that Regulator is in NEUTRAL position (Position indicator & FC12) 7. Set Power switch & control switch to OFF position (All three switches in middle ) 8. In Control back panel OPEN knife switch V1, C (and V6 if present), (pulled out) (Terminal links) 9. Insulation test must be done ( 5KV Megger ) Ohm 10. Close Source-Load (SL) incoming link (Operator to close) CHECK THAT ALL 3 PHASES ARE PRESENT IN AND OUT 11. Measure Voltage terminal V1 to earth and confirm approx 118-122VAC (If out of range, abort commissioning and investigate) Volt R = W= B= 12. In Control back panel CLOSE knife switch V1 (and V6 if present), (pushed in) (Terminal links) 13. Check that knife switch “C” is open (Terminal links) 14. Set Power Switch to INTERNAL (Power switch up) Set Clock ( FC 50 ) 15. Check NEUTRAL light is on 16. Check settings according to settings sheet (Annexure) (Note: for testing of up/down tap, set FC56 to Lock Forward) 17. Set control switch to MANUAL (Control switch down) 18. Manually RAISE tap till Out of Band indication ON 19. Set control switch to AUTO (Control switch up) 20. Confirm auto-tap LOWER & Out of Band indication OFF (FC3 Delay plus 2sec per tap)
  • 49. • Evaluation of losses in step-voltage regulators is increasingly a major consideration when evaluating competitive alternatives. . Some of the areas that should be evaluated in addition to the cost : • Maintenance, • Installation and Operation, • Technical support, • Dielectric strength, • Short circuit strength, • Losses 49 Regulator Characteristics
  • 50. Thank you Open for Discussion